| Share On: | |
|---|---|
| Categories: | Zigbee Wireless Modbus RTU Data Acquisition | Zigbee Wireless Modbus RTU Data Acquisition | Zigbee Alliance Based Wireless | Zigbee Alliance Based Wireless Products |
| Review: | Write your review |
| Resources: |
The ZT-2026 is a wireless ZigBee module that offers 4 differential analog input channels, 2 analog output channels, 2 digital input channels and 2 digital output channels and provides a programmable analog input and output range. Each analog input channel can be configured to an individual range and each has 240 Vrms overvoltage protection. There are also options for a power-on value and a safe value. Users can easily confi gure the module address, protocol, checksum, ZT-PID, ZT-channel and type code settings using a combination of rotary and DIP switches.
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote Diagnosis, Testing Equipment.
| Communication Interface | |
| Wireless Standards | ZigBee 2007 Pro |
| Transmission Power | 11 dBm(FCC Certificated) ( Max 19 dBm) |
| 2.4 GHz Antenna | 5 dBi Omni directional |
| Transmission Range (LoS) | 700 m (Typical) |
| Certification | CE/FCC, FCC ID |
| Max. Slaves in a ZigBee Network | 255 |
| ZB-100R/ZB-100T Support | - |
| Protocols | Supports DCON and Modbus RTU Protocols |
| Hot Swap | Rotary and DIP switch |
| LED Indicators | |
| Power | 1 LED, red |
| ZigBee Communication | 1 LED, green |
| Isolation | |
| Intra-module Isolated, Field-to-Logic | 2500 VDC (for AI, AO, DI and DO) |
| EMS Protection | |
| ESD (IEC 61000-4-2) | 4 kV Contact for Power Line, Communication Line and each Channel, 8 kV Air for Random Point |
| EFT (IEC 61000-4-4) | 4 kV for Power Line |
| Power | |
| Input Voltage Range | +10 VDC ~ +30 VDC (Reverse Polarity Protection) |
| Power Consumption | 2.1 W Max. |
| Mechanical | |
| Flammability | Fire Retardant Materials (UL94-V0 Level) |
| Dimensions (W x L x H) | 33 mm x 87 mm x 107 mm |
| Installation | DIN-Rail |
| Environment | |
| Operating Temperature | -25 °C ~ +75 °C |
| Storage Temperature | -30 °C ~ +80 °C |
| Relative Humidity | 10 ~ 90% RH, Non-condensing |
| Analog Input | |
| Input Channels | 4 Differential |
| Input Types | +/-10 V, +/-5 V, +/-1 V, +/-500 mV, +/-150 mV or -20 mA ~ +20 mA (Requires Optional External 125 Ω Resistor) |
| Resolution | 16-bit |
| Sampling Rate | 10 Samples/Second (Total) |
| Accuracy | +/-0.1% of FSR |
| -3dB Bandwidth | 15.7 Hz |
| Zero Drift | +/-20 μV/°C |
| Span Drift | +/-25 ppm/°C |
| Common Mode Rejectio | 86 dB |
| Normal Mode Rejection | 100 dB |
| Input Impedance | >2 MΩ |
| Overvoltage Protection | 240 Vrms |
| Individual Channel Confi guration | Yes |
| Analog Output | |
| Output Channels | 2 |
| Output Types | +/-10 VDC, +/-5 VDC, 0 ~ 10 VDC or 0 ~ 5 VDC |
| Resolution | 12-bit |
| Accuracy | +/-0.1% of FSR |
| Zero Drift | +/-30 μV/°C |
| Span Drift | +/-25 ppm/°C |
| Programmable Output Slope | 0.0625 ~ 512 V/Second |
| Voltage Capability | 20 mA @ 10 V |
| Power-on and Safe Value | Yes |
| Digital Input | |
| Input Channels | 2 (Sink) |
| On Voltage Level | 3.5 VDC ~ 50 VDC |
| Off Voltage Level | 1 VDC Max. |
| Input Impedance | 10 KΩ |
| Event Counters | Channels : 2 |
| Max. Count: 16-bit (65535) | |
| Max. Input Frequency: 50 Hz | |
| Min. Pulse Width: 10 ms | |
| Digital Output | |
| Output Channels | 2 (Sink) |
| Output Types | Isolated Open Collector |
| Max. Load Current | 700 mA/channel |
| Load Voltage | +5 VDC ~ +50 VDC |
| Short Circuit Protection | Yes |
Our mission is to provide the absolute best customer experience in industrial automation and electronics, without exception.
Subscribe to our mailing list today and join thousands of others who want to stay up-to-date with the latest news in data acquisition and industrial data communication.
Add a review