The tM-P4A4 provides 4 channels for digital input and 4 channels for digital output, each of which features photocouple isolation. The tM-P4A4 supports source type output with short circuit protection, while input is sink type. All input channels can be used an 16-bit counters. There are options for configuring power-on and safe digital output values. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided.
| CPU Module | |
|---|---|
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
|---|---|
| Intra-module Isolation | 3750 VDC |
| EMS Protection | |
|---|---|
| EFT (IEC 61000-4-4) | ±4 kV for Power |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
| LED Indicators | |
|---|---|
| Status | 1 x Power and Communication |
| Digital Input/Counter | |
|---|---|
| Channels | 4 |
| Type | Wet Contact |
| Sink/Source (NPN/PNP) | Sink |
| ON Voltage Level | +4.0 ~ +50 VDC |
| OFF Voltage Level | +1 VDC max. |
| Max. Counts | 65535 (16-bit) |
| Frequency | 100 Hz |
| Min. Pulse Width | 5 ms |
| Input Impedance | 10 K, 0.66 W |
| Overvoltage Protection | 70 VDC |
| Digital Output | |
|---|---|
| Channels | 4 |
| Type | Isolated Open Collector |
| Sink/Source (NPN/PNP) | Source |
| Load Voltage | +10 ~ +40 VDC |
| Load Current | 650 mA/channel |
| Overvoltage Protection | 47 VDC |
| Overload Protection | 1.4 A |
| Short-circuit Protection | Yes |
| Power on Value | Programmable |
| Safe Value | Programmable |
| COM Ports | |
|---|---|
| Ports | 1 x RS-485 |
| Baud Rate | 1200 ~ 115200 bps |
| Data Format | (N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1) |
| Protocol | DCON, Modbus RTU, Modbus ASCII |
| Power | |
|---|---|
| Reverse Polarity Protection | Yes |
| Consumption | 0.5 W max. |
| Powered from Terminal Block | 10 ~ 30 VDC |
| Mechanical | |
|---|---|
| Dimensions (mm) | 52 x 98 x 27 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
|---|---|
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +75 °C |
| Humidity | 10 ~ 95% RH, Non-condensing |