| Share On: | |
|---|---|
| Categories: | DeviceNet Data Acquisition |
| Review: | Write your review |
| Resources: |
The CAN-2015D is an 8 Channel RTD Analog input DeviceNet slave device. RTD input status and configuration of CAN-2015D can be done through the EDS file. DeviceNet heartbeat and shutdown messages can also be done with this device.
This device is in compliance with DeviceNet specification Volume 1 Release 2.0 and Volume 2 Release 2.0, Errata 5. This is also a Group 2 Only Server (non-UCMM-capable) device. A predefined Master/Slave Connection Set is one of its features. Supported connections are the following: 1 connection for Explicit Messaging, 1 connection for Polled I/O, and 1 connection for Bit0Strobe I/O connection.
DeviceNet Interface |
|
Channels |
8 |
Wiring |
2/3 Wire |
Individual Channel |
Yes |
Sensor Type |
RTD (Pt100, Pt1000, Ni120, Cu100, Cu1000, Pt100) |
Voltage Input Range |
- |
| Current Input Range | - |
| Resolution | 16-bit |
| Sampling Rate | 10 Hz |
| Accuracy | ±0.05 % of FSR |
| Zero Drift | ±0.5 μV/ °C |
| Span Drift | ±20 μV/ °C |
| Overvoltage Protection | 240 Vrms |
| Input Impedence | 20 MΩ |
| Common Mode Rejection | 150 d |
| Normal Mode Rejection | 100 dB |
Communication |
|
| Connector | 5-pin screwed terminal block (CAN_GND, CAN_L, CAN_SHLD, CAN_H, CAN_V+) |
| Baud Rate (bps) | 125 k, 250 k, 500 k |
| Terminator Resistor | Switch for 120 Ω terminator resistor |
| Node ID | 0~63 selected by rotary switch |
| Protocol | Volume I, Release 2.0 & Volume II, Release 2.0, Errata 5 |
| DeviceNet Subscribe | Group 2 Only Server |
| Explicit Connection | Yes |
| Polled I/O Connection | Yes |
| Bit-Strobe I/O Connection | Yes |
| Heartbeat message | Yes |
| Shutdown message | Yes |
System |
|
| ESD Protection | 4 kV Contact for each channel |
| Isolation | 3000 VDC for DC-to-DC, 2000 Vrms for bus-to-logic |
Watchdog |
Yes |
Power |
|
Input Range |
Unregulated +10 ~ +30 VDC |
Power Consumption |
1.5 W |
Mechanism |
|
| Installation | DIN-Rail |
Dimensions |
33 mm x 107 mm x 102 mm ( W x L x H ) |
Environmental |
|
Operating Temperature |
-25°C ~ +75°C (-13°F ~ +167°F) |
Storage Temperature |
-30°C ~ +80°C (-22°F ~ +176°F) |
Ambient Relative Humidity |
10 ~ 90% RH, non-condensing |