| Share On: | |
|---|---|
| Categories: | Wi-Fi Modbus TCP Data Acquisition | Wi-Fi Data Acquisition | New Products | Industrial Wi-Fi Data Acquisition Modules |
| Review: | Write your review |
| Resources: |
The ALM-06-WF controller have WLAN connection complies with the IEEE802.11b/g/n standards. With the popularity of 802.11 network infrastructure, the controller make an easy way to incorporate wireless connectivity into monitoring and control systems. They also support Modbus TCP monitoring protocol and the network encryption configuration, which makes perfect integration to monitoring in SCADA software, HMI Modbus APP & Utility. ALM-06-WF include 6 channels Isolated DI, with 8 kinds of alarm mode, 1 channel Relay output & 1 Audio Line out. MP3 format(44.1kHz/128kbit/s is perfer) Audio, file stored at Micro SD(T-Flash).
Digital Input
Channels
6
Input Type
Dry Contact: Sink
Dry Contact Level
Off Voltage Level: Open
On Voltage Level: Close to GND
Photo-Isolation
3750 VDC
Input Condition
Pulse Width must > 150mSec or more
Digital Output
Channels
1
Output Type
Form A Relay
Contact Rating
DC 50V/100mA
Audio
Sound Pressure Level
99dB@1KHz/1meter
Volume Control
Digital Volume Control
Number of File
64(Max)
Audio File Format
MPEG1-Audio Layer III (MP3)
Sample Rate
24/44.1(prefer)/48 KHz
Bit Rate
32 64 96 128(prefer) 160 192 kbit/s
Audio Startup Time
< 150ms
Audio Output
3W(Max)
Line out Impedance
1KΩ
Storage
Audio Files Locate
Micro SD(T-Flash) up to 32GB, bundle 4GB
Storage File System
Fat16/32
File Transfer
PC Utility through Wi-Fi
Communication
Interface
Wi-Fi 2.4G
Standard
IEEE 802.11 b/g/n
Encryption
WEP, WPA/WPA2-PSK
Mode
Access Point (AP) & Station (STA)
IP Configuration
DHCP Server (AP, 1 client), DHCP Client, Static IP (STA)
Service
TCP, Modbus TCP
LED Indicators
Power/Status
One 2 colors LED, Blue for System status, Purple(Blue+Red)for Connective status/Locator
Isolation
Intra-module Isolation, Field-to-Logic
3000 VDC
Protection
ESD (IEC 61000-4-2)
±8 kV Air for Random Point
EFT (IEC 61000-4-4)
±2 kV for Power
Waterproof(IEC 60529)
IP54 (Panel Mount Upright Position)
Power Requirements
Powered from Connector
9 ~ 28 VDC with Reverse Protection(Vin to GND)
Consumption
0.7 W Standby
Mechanical
Dimensions (W x L x H)
72 mm x 72 mm x 22 mm
Installation
Panel Mount/Wall Mount/DIN-Rail Mounting
Environment
Operating Temp.
-20°C ~ +75°C
Storage Temp.
-30°C ~ +85°C
Humidity
10 ~ 85% RH, non-condensing
Our mission is to provide the absolute best customer experience in industrial automation and electronics, without exception.
Subscribe to our mailing list today and join thousands of others who want to stay up-to-date with the latest news in data acquisition and industrial data communication.
Add a review