The ZT-2060 offers 4 Form A power relay output channels and 6 digital input channels, each of which features photocouple isolation. In addition, you can choose sink-type or source-type input via wire connections. All channels are able to be used as 16-bit counters. The ZT-2060 has 10 LED indicators to display the channel status, and has 4 kV ESD protection and 3000 VDC intramodule isolation. Users can easily configure the module address, protocol, checksum, ZB-PID and ZB-channel settings using a combination of rotary and DIP switches.
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote Diagnosis, Testing Equipment.
| Digital Input | ||
| Input Channels | 6 | |
| Input Types | Isolated, Wet Contact (Sink/Source) | |
| Input Level | On Voltage Level | +3.5 VDC ~ +30 VDC |
| Off Voltage Level | +1 VDC Max. | |
| Input Impedance | 3 kΩ, 0.33 W | |
| Counter | Channels | 6 |
| Max. Count | 16-bit (65535) | |
| Max. Input Frequency | 100 Hz | |
| Min. Pulse Width | 5 ms | |
| Relay Output | ||
| Output Channels | 4 | |
| Output Types | Power Relay, Form A | |
| Contact Rating | 5 A @ (250 VAC/30 VDC) | |
| Max. Contact Voltage | 270 VAC/125 VDC | |
| Operate Time | 10 ms max. at Rated Voltage | |
| Release Time | 5 ms max. at Rated Voltage | |
| Endurance | Electrical | Resistive Load: 100,000 ops. min. (10 ops/minute) |
| Mechanical | At No Load: 20,000,000 ops. min. (300 ops/minute) | |
| Dielectric Strength | Between Contacts | 750 VAC for 1 minute |
| Between Coil to Contacts | 3,000 VAC for 1 minute | |
| Insulation Resistance | 5,080 V (1.2/50 μs) | |
| Surge Strength | 5 ms max. at Rated Voltage | |
| ESD Protection | +/-4 kV contact for each channel | |
| Communication Interface | ||
| Wireless Standards | ZigBee 2007 Pro | |
| Transmission Power | 11 dBm (FCC Certificated) | |
| 2.4 GHz Antenna | 5 dBi Omni directional | |
| Transmission Range (LoS) | 700 m (Typical) | |
| Certification | CE/FCC, FCC ID | |
| Max. Slaves in a ZigBee Network | 255 | |
| Protocols | Supports DCON and Modbus RTU Protocols | |
| Hot Swap | Rotary and DIP switch | |
| LED Indicators | ||
| Power | 1 LED, Red | |
| ZigBee Communication | 1 LED, Green | |
| Digital Input and Output | 6 Green LEDs for Digital Input 4 Red LEDs for Relay Output |
|
| Isolation | ||
| Intra-module Isolated, Field-to-Logic |
2500 VDC | |
| EMS Protection | ||
| ESD (IEC 61000-4-2) | 4 kV Contact for Power Line, Communication Line and each Channel, 8 kV Air for Random Point |
|
| EFT (IEC 61000-4-4) | 4 kV for Power Line | |
| Power | ||
| Input Voltage Range | +10 VDC ~ +30 VDC | |
| Power Consumption | 1.4 W Max. | |
| Mechanical | ||
| Flammability | Fire Retardant Materials (UL94-V0 Level) | |
| Dimensions (W x L x H) | 33 mm x 94 mm x 110 mm | |
| Installation | DIN-Rail | |
| Environment | ||
| Operating Temperature | -25 ~ +75°C | |
| Storage Temperature | -30 ~ +80°C | |
| Relative Humidity | 10 ~ 90% RH, Non-condensing | |