WISE-7102 (Web Inside, Smart Engine) is a device developed by ICP DAS USA that functions as a control units for use in remote logic control and monitoring in various industrial applications. WISE offers a user-friendly and intuitive web site interface that allows users to implement IF-THEN-ELSE control logic on controllers with just a few clicks; no programming is required. With its powerful and easy-to-use features, it minimizes the learning curve, shorten time to market, and dramatically reduce effort and cost spent on system development.
The WISE-7102 follows IEEE 802.3af-compliant (classification, Class 1) Power over Ethernet (PoE) specification. It allows receiving power from PoE enabled networks by Ethernet pairs (Category 5 Ethernet cable). This feature provides greater flexibility and higher efficiency therefore simplifying systems design, saving space, reducing cables and eliminating the requirement for dedicated electrical outlets. For cases under a non-PoE environment, WISE-7102 will still be able to receive power from auxiliary power sources like AC adapters or battery, etc.
This multi-function module WISE-7102 supports Modbus TCP protocol for seamless integration with SCADA software available. It features 3-channel analog inputs, 6-channel digital inputs and 3-channel Power Relay outputs. Each analog input channel provides 240 Vrms high over voltage protection.
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Functions | |
| 36 IF-THEN-ELSE Logic Rules | 3 IF conditions with AND or OR operators per rule 3 THEN actions per rule 3 ELSE actions per rule |
| 48 Internal Registers | Hold temporary variables and read/write data via Modbus/TCP address. |
| 12 Timers | Delay / Timing functions. |
| 12 Emails | Send Email messages to pre-set Email receivers. |
| 12 CGI Commands | Send pre-set CGI commands. |
| 12 Receipts | Set up Then/ELSE action groups. |
| Rule Configuration Website | Access Web server on WISE controllers to edit and upload logic rules through web browser. |
| Modbus/TCP Protocol | Real time control and monitoring I/O channels and system status of controllers via SCADA software. |
| IF Conditions | |
| AI Channel | ON、OFF、ON to OFF、OFF to ON、Change |
| Internal Register | =、>、<、>=、<=(value) |
| Rule Status | Enable、Disable |
| P2P | DI、AI、DI counter、DO counter、IR |
| DO Counter | =、>、<、>=、<=(value)、Change |
| Timer | Timeout、Not Timeout |
| THEN / ELSE Actions | |
| DO Channel | ON、OFF、Pulse Output |
| Internal Register | Change the value |
| DO Counter | Reset |
| Timer | Start、Stop |
| Start、Stop | |
| CGI Commands | |
| Recipe | Execute |
| P2P | DO(On/Off)、AO、IR |
| Rule Status | Enable、Disable |
Our mission is to provide the absolute best customer experience in industrial automation and electronics, without exception.
Subscribe to our mailing list today and join thousands of others who want to stay up-to-date with the latest news in data acquisition and industrial data communication.
Add a review
Your email address will not be published. Required fields are marked *