The tM-P3R3 provides 3 channels for digital input and 3 channels for relay output, each of which features photocouple isolation. All output channels are form A type relays, while input is based on sink- or souce-type using a wire connecion. All input channels can be used an 16-bit counters. There are options for configuring power-on and safe digital output values. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided.
| Digital Input/Counter | ||
| Input Channels | 3 | |
| Type | Wet Contact (Sink, Source) | |
| On Voltage Level | +3.5 VDC ~ 50 VDC | |
| Off Voltage Level | +1 V Max. | |
| Input Impedance | 10 KΩ, 0.66 W | |
| Counters | Channels | 3 |
| Max. Count | 65535 (16-bit) | |
| Max. Input Frequency | 100 Hz | |
| Min. Pulse Width | 5 ms | |
| Overvoltage Protection | 70 VDC | |
| Relay Output | ||
| Output Channels | 3 | |
| Type | Power Relay, Form A (SPST N.O.) | |
| Operating Voltage Range | 250 VAC or 30 VDC | |
| Max. Load Current | 5 A | |
| Operating Time | 6 ms | |
| Release Time | 3 ms | |
| Electrical Life (Resistive load) |
VDE | 5 A @250 VAC 30,000 ops (10 ops/minute) at 75°C |
| 5 A @30 VDC 70,000 ops (10 ops/minute) at 75°C | ||
| UL | 5 A @250 VAC/30 VDC 6,000 ops | |
| 3 A @250 VAC/30 VDC 100,000 ops | ||
| Mechanical Life | 20,000,000 ops at no load (300 ops/minute) | |
| Power-on Value | Yes, Programmable | |
| Safe Value | Yes, Programmable | |
| Communication | ||
| Interface | RS-485 | |
| Format | (N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1) | |
| Baud Rate | 1200 ~ 115200 bps | |
| Protocol | DCON, Modbus/RTU, Modbus/ASCII | |
| Dual Watchdog | Yes, Module (2.3 seconds), Communication (Programmable) | |
| LED Indicators | ||
| Power | 1 LED as Power Indicator | |
| Isolation | ||
| Intra-module Isolation,Field-to-Logic | 3750 VDC | |
| EMS Protection | ||
| ESD (IEC 61000-4-2) | +/-4 kV Contact for Each Terminal | |
| +/-8 kV Air for Random Point | ||
| EFT (IEC 61000-4-4) | +/-4 kV for Power | |
| Power Requirements | ||
| Reverse Polarity Protection | Yes | |
| Powered from Terminal Block | Yes, 10 ~ 30 VDC | |
| Consumption | 0.5 W Max. | |
| Mechanical | ||
| Dimensions (W x L x H) | 52 mm x 98 mm x 27 mm | |
| Installation | DIN-Rail Mounting | |
| Environment | ||
| Operating Temperature | -25 °C ~ +75 °C | |
| Storage Temperature | -30 °C ~ +75 °C | |
| Humidity | 10 ~ 95% RH, Non-condensing | |
Our mission is to provide the absolute best customer experience in industrial automation and electronics, without exception.