The M-7045D supports sourcetype output, while the M-7045D-NPN supports sink-type, and both are equipped with short circuit protection. There are options to enable both power-on and safe values, and 16 LED indicators that can be used to monitor the status of the digital output channels. 4 kV ESD protection, 4 kV EFT protection, 3 kV surge protection for power input and 3750 VDC Intra-module isolation are standard.
The M-7045D device is network data acquisition and control modules that support Modbus RTU. They can be remotely controlled using a set of commands called DCON protocol. With the Modbus RTU protocol, it can easily communicate with most popular SCADA/ HMI software and PLCs.
| CPU Module | |
|---|---|
| Watchdog Timer | Module, Communication (Programmable) |
| Display | |
|---|---|
| Type | I/O LED Indicator |
| Isolation | |
|---|---|
| Intra-module Isolation | 3750 VDC |
| EMS Protection | |
|---|---|
| EFT (IEC 61000-4-4) | ±4 kV for the 16 DO channels and Power, ±2 kV for the RS-485 Port |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
| Surge (IEC 61000-4-5) | ±3 kV for Power Line |
| LED Indicators | |
|---|---|
| Status | 1 x Power and Communication 16 x Digital Output |
| Digital Output | |
|---|---|
| Channels | 16 |
| Type | Open Source |
| Sink/Source (NPN/PNP) | Source |
| Load Voltage | +10 ~ +40 VDC |
| Load Current | 650 mA/Channel |
| Overvoltage Protection | 47 VDC |
| Overload Protection | 1.4 A |
| Short-circuit Protection | Yes |
| Power on Value | Programmable |
| Safe Value | Programmable |
| COM Ports | |
|---|---|
| Ports | 1 x RS-485 |
| Baud Rate | 1200 ~ 115200 bps |
| Data Format | (N, 8, 1) |
| Protocol | Modbus RTU, DCON |
| Power | |
|---|---|
| Reverse Polarity Protection | Yes |
| Input Range | +10 ~ +30 VDC |
| Consumption | 1.5 W |
| Mechanical | |
|---|---|
| Dimensions (mm) | 72 x 123 x 35 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
|---|---|
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -40 ~ +85 °C |
| Humidity | 10 ~ 95% RH, Non-condensing |