| Share On: | |
|---|---|
| Categories: | M-7000 Modbus RTU Remote Data Acquisition Modules | M-7000 Modbus RTU Remote Data Acquisition Modules |
| Review: | Write your review |
| Resources: |
The M-7015 device is a network data acquisition and control modules that support Modbus RTU. They can be remotely controlled using a set of commands called DCON protocol. With the Modbus RTU protocol, it can easily communicate with most popular SCADA/ HMI software and PLCs.
| Analog Input | |
| Input Channels | 6 |
| Input Type | RTD |
| Wire connection | 2/3 wire |
| RTD Type | Pt100, Pt1000, Ni120, Cu100, Cu1000 |
| Resolution | 16-bit |
| Sampling Rate | 12 samples/ second (Total) |
| Accuracy | +/-0.05% |
| -3dB BandWidth | 5.24Hz |
| Zero drift | +/-20uV/°C |
| Span drift | +/-25ppm/°C |
| Common Mode Rejection | Typical 86dB |
| Normal Mode Rejection | 100 dB |
| Voltage Input Impedance | >1M Ohms |
| Open Wire Detection | Yes |
| Individual Channel Configurable | Yes |
| 4KV ESD Protection | Yes, Contact for each terminal. |
| Intra-module Isolation, Field to Logic | 3000 VDC |
| Interface | |
| Interface | RS-485 |
| Format | N, 8, 1 |
| Baud Rate | 1200 ~ 115200bps |
| LED Display | |
| 1 LED as Power/ Communication indicator | |
| Power | |
| Input | +10 to +30 Vdc |
| Power Consumption | 1.1W |
| Protocol | |
| Support Modbus and DCON Protocol | Yes |
| Watchdog | Yes, Module, Communication (Programmable over DCON) firmware version B202 and later |
| Environment | |
| Operating temperature | -25 to 75°C |
| Storage temperature | -40 to 85°C |
| Humidity | 5 to 95% RH, non-condensing |
| NOTE: We recommend to chose M-7015P for long distance RTD Line. | |
| Type Code | RTD Type | Temperature Range °C |
| 20 | Platinum 100, α= 0.00385 | -100 ~ 100 |
| 21 | Platinum 100, α= 0.00385 | 0 ~ 100 |
| 22 | Platinum 100, α= 0.00385 | 0 ~ 200 |
| 23 | Platinum 100, α= 0.00385 | 0 ~ 600 |
| 24 | Platinum 100, α= 0.003916 | -100 ~ 100 |
| 25 | Platinum 100, α= 0.003916 | 0 ~ 100 |
| 26 | Platinum 100, α= 0.003916 | 0 ~ 200 |
| 27 | Platinum 100, α= 0.003916 | 0 ~ 600 |
| 28 | Nickel 120 | -80 ~ 100 |
| 29 | Nickel 120 | 0 ~ 100 |
| 2A | Platinum 1000, α= 0.00385 | -200 ~ 600 |
| 2B | Cu 100 at 0°C,α= 0.00421 | -20 ~ 150 |
| 2C | Cu 100 at 25°C,α= 0.00427 | 0 ~ 200 |
| 2D | Cu 1000 at 0°C,α= 0.00421 | -20 ~ 150 |
| 2E | Platinum 100, α= 0.00385 | -200 ~ 200 |
| 2F | Platinum 100, α= 0.003916 | -200 ~ 200 |
| 80 | Platinum 100, α= 0.00385 | -200 ~ 600 |
| 81 | Platinum 100, α= 0.003916 | -200 ~ 600 |
| 82 | Cu 50 at 0°C | -50 ~ 150 |
| 83 | Nickel 100 | -60 ~ 180 |