| Share On: | |
|---|---|
| Categories: | M-7000 Modbus RTU Remote Data Acquisition Modules | M-7000 Modbus RTU Remote Data Acquisition Modules |
| Review: | Write your review |
| Resources: |
The M-7002 is a 16-bit, 4-channel differential analog inputs 5-channel digital inputs and 4-channels for relay output. All of its channels are Form A type relay module that provides programmable input range on all analog channels (+/-150 mV, +/-500 mV, +/-1 V, +/-5 V, +/-10 V, +/-20 mA, 0 ~ 20 mA and 4 ~ 20 mA) and digital output can be set alarm output with shortcircuit protection and overload protection. Each analog channel is allowed to configure an individual range and has 240 Vrms high overvoltage protection. Jumper selectable for voltage or current input. The sampling rate of M-7002 is changeable; there are fast mode and normal mode for your consideration. M-7002 also has qualification for 4 kV ESD protection as well as 2500 VDC intra-module isolation.
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote Diagnosis, Testing Equipment.
| Analog Input | ||
| Channel | 4 | |
| Wiring | Differential | |
| Input Range | +/-150 mV, +/-500 mV, +/-1 V , +/-5 V, +/-10 V +/-20 mA , 0~20 mA, 4~20 mA (Jumper selectable) |
|
| Resolution | 12/16-bit | |
| Accuracy | Normal Mode | 0.1% |
| Fast Mode | 0.5% | |
| Sampling Rate | Normal Mode | 10 Hz |
| Fast Mode | 60 Hz | |
| Input Impedance | Voltage | 2 M |
| Currnet | 139 Ω | |
| Common Voltage Protection | +/-200 VDC | |
| Individual Channel Configuration | Yes | |
| Overvoltage Protection | 240 Vrms | |
| Digital Input/Counter | ||
| Channel | 5 | |
| Contact | Wet | |
| Sink/Source (NPN/PNP) | Sink/Source | |
| On Voltage Level | 10 ~ 50 VDC | |
| Off Voltage Level | +4 VDC Max. | |
| Counter (50 Hz, 16-bit) | Yes | |
| Input Impedance | 10 kΩ | |
| Overvoltage Protection | +/-70 VDC | |
| Isolation Voltage | 3750 VDC | |
| Relay Output | ||
| Channel | 4 | |
| Type | Power Relay (Form A) | |
| Contact Rating | 5 A @ 250 VAC 5 A @ 30 VDC |
|
| Surge Strength | 3000 VDC | |
| Operate Time | 6 ms | |
| Release Time | 3 ms | |
| Mechanical Endurance | 2 × 107 ops. | |
| Electrical Endurance | 105 ops. | |
| Power-on Value | Yes | |
| Safe Value | Yes | |
| Communication | ||
| Interface | RS-485 | |
| Format | N, 8, 1 | |
| Baud Rate | 1200 ~ 115200bps | |
| Protocol | DCON Modbus/RTU | |
| Watchdog | Yes, Module, Communication (Programmable) | |
| LED Indicator/Display | ||
| System LED Indicator | Yes, 1 LED as Power/Communication Indicator | |
| I/O LED Indicator | - | |
| 7-Segment LED Display | Yes | |
| Isolation | ||
| Intra-Module Isolation, Field-to-Logic | 2500 VDC | |
| EMS Protection | ||
| ESD (IEC 61000-4-2) | +/-4 kV | |
| EFT (IEC 61000-4-4) | +/-4 kV | |
| Surge (IEC 61000-4-5) | +/-3 kV | |
| Power | ||
| Reverse Polarity Protection | Yes | |
| Input Voltage Range | 10 ~ 30 VDC | |
| Consumption | 1.8 W | |
| Mechanical | ||
| Dimensions (W x L x H) | 72 mm x 123 mm x 35 mm | |
| Installation | DIN-Rail or Wall Mounting | |
| Environment | ||
| Operating Temperature | -25 ~ +75°C | |
| Storage Temperature | -40 ~ +85°C | |
| Humidity | 10 ~ 95% RH, Non-condensing | |
Our mission is to provide the absolute best customer experience in industrial automation and electronics, without exception.