| Share On: | |
|---|---|
| Categories: | M-7000 Modbus RTU Remote Data Acquisition Modules | M-7000 Modbus RTU Remote Data Acquisition Modules |
| Review: | Write your review |
| Resources: |
The M-7052 device is a data acquisition and control modules that support Modbus RTU. They can be remotely controlled using a set of commands called DCON protocol. With the Modbus RTU protocol, it can easily communicate with most popular SCADA/ HMI software and PLCs.
| Communication | |
| Interface | RS-485 |
| Bias Resistor | No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.) |
| Format | (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
| Baud Rate | 1200 to 115200 bps |
| Logic level 1: +3.5 to 30V | |
| Protocol | Modbus RTU, DCON |
| Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) |
| LED Indicators/Display | |
| System LED Indicator | Yes, 1 as Power/Communication Indicator |
| I/O LED Indicators | Yes, 8 LEDs as Digital Input Indicators |
| 7-Segment LED Display | - |
| Isolation | |
| Intra-module Isolation, Field-to-Logic | 5000 Vrms |
| EMS Protection | |
| ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal |
| ±8 kV Air for Random Point | |
| EFT (IEC 61000-4-4) | ±2 kV for Power Line |
| Surge (IEC 61000-4-5) | - |
| Power | |
| Reverse Polarity Protection | Yes |
| Input Range | 10 ~ 30 VDC |
| Consumption | 0.2 W |
| Mechanical | |
| Dimensions (L x W x H) | 123 mm x 72 mm x 35 mm |
| Installation | DIN-Rail or Wall Mounting |
| Environment | |
| Operating Temperature | -25°C ~ +75°C (-13°F ~ +167°F) |
| Storage Temperature | -40°C ~ +85°C (-40°F ~ +185°F) |
| Humidity | 10 ~ 95% RH, Non-condensing |
| Digital Input/Counter | ||
| Channels | 8 | |
| Type | Dry Contact | - |
| Wet Dry | Sink/Source | |
| Wet Contact | On Voltage Level | +4 ~ 30 VDC |
| Off Voltage Level | +1 VDC Max. | |
| Dry Contact | On Voltage Level | - |
| Off Voltage Level | - | |
| Effective Distance for Dry Contact | - | |
| Counters | Max. Count | 65535 (16-bit) |
| Max. Input | 100 hz | |
| Min. Pulse Width | 5 ms | |
| Input Impedence | 3 KΩ | |
| Chanell-to-Channel Isolation | - | |
| Overvoltage Protection | ±35 VDC | |
Our mission is to provide the absolute best customer experience in industrial automation and electronics, without exception.
Subscribe to our mailing list today and join thousands of others who want to stay up-to-date with the latest news in data acquisition and industrial data communication.
Add a review