| Share On: | |
|---|---|
| Categories: | I-7000 Remote Data Acquisition Modules via RS-485 / DCON Protocol |
| Review: | Write your review |
| Resources: |
The I-7015P device is designed for temperature measurement plus wide connection with 6 input channels. In order to reduce the signal collapse, we develops auto-compensation to double the delivering distance. I-7015P supports several kinds of RTD, has passed 4000V ESD protection and fits in with all kinds of rough industrial environment.
| Analog Input | |
| Input Channels | 6 |
| Input Type | RTD |
| Wire connection | 2/3 wire |
| RTD Type | Pt100, Pt1000, Ni120, Cu100, Cu1000 |
| Resolution | 16-bit |
| Sampling Rate | 12 samples/ second (Total) |
| Accuracy | +/-0.05% |
| -3dB BandWidth | 15.7Hz |
| Zero drift | +/-0.5μV/°C |
| Span drift | +/-20μV/°C |
| Common Mode Rejection | 150 dB |
| Normal Mode Rejection | 100 dB |
| Voltage Input Impedance | >1M Ohms |
| Open Wire Detection | Yes |
| Individual Channel Configurable | Yes |
| 3-wire RTD lead resistance elimination | Yes |
| ESD Protection | 4KV Contact for each terminal, and 8KV Air for random point |
| EFT Protection | 4KV to Power, and 1KV to RS-485 |
| Intra-module Isolation, Field to Logic | 3000 VDC |
| Interface | |
| Interface | RS-485 |
| Format | N, 8, 1 |
| Baud Rate | 1200 ~ 115200bps |
| LED Display | |
| 1 LED | as Power/ Communication indicator |
| Power | |
| Input | +10 to +30 Vdc |
| Power Consumption | 1.2W |
| Environment | |
| Operating temperature | -25 to 75°C |
| Storage temperature | -40 to 85°C |
| Humidity | 5 to 95%, non-condensing |
| Type Code | RTD Type | Temperature Range °C |
| 20 | Platinum 100, α= 0.00385 |
-100 ~ 100 |
| 21 | Platinum 100, α= 0.00385 |
0 ~ 100 |
| 22 | Platinum 100, α= 0.00385 |
0 ~ 200 |
| 23 | Platinum 100, α= 0.00385 |
0 ~ 600 |
| 24 | Platinum 100, α= 0.003916 |
-100 ~ 100 |
| 25 | Platinum 100, α= 0.003916 |
0 ~ 100 |
| 26 | Platinum 100, α= 0.003916 |
0 ~ 200 |
| 27 | Platinum 100, α= 0.003916 |
0 ~ 600 |
| 28 | Nickel 120 |
-80 ~ 100 |
| 29 | Nickel 120 |
0 ~ 100 |
| 2A | Platinum 1000, α= 0.00385 |
-200 ~ 600 |
| 2B | Cu 100 at 0°C,α= 0.00421 |
-20 ~ 150 |
| 2C | Cu 100 at 25°C,α= 0.00427 |
0 ~ 200 |
| 2D | Cu 1000 at 0°C,α= 0.00421 |
-20 ~ 150 |
| 2E | Platinum 100, α= 0.00385 |
-200 ~ 200 |
| 2F | Platinum 100, α= 0.003916 |
-200 ~ 200 |
| 80 | Platinum 100, α= 0.00385 |
-200 ~ 600 |
| 81 | Platinum 100, α= 0.003916 |
-200 ~ 600 |