| Share On: | |
|---|---|
| Categories: | Remote Ethernet Modbus TCP I/O Modules |
| Review: | Write your review |
| Resources: |
The ET-7017-10 is a Modbus TCP based 16-bit, 10-channel differential or 20-channel single-ended analog input data acquisition module that provides programmable input range on all analog channels (+/-150mV, +/-500mV, +/-1V, +/-5V, +/-10V, +/-20mA, 0~20mA and 4~20mA). Each analog channel is allowed to configure an individual range and has 240Vrms high voltage protection. Jumper is selectable for voltage or current input. It can be used with LabView from National Instruments, Indusoft SCADA Software, Free EZ Data Logger and other software that supports Modbus TCP protocol.
The ET-7017-10 is a web-based Ethernet I/O data acquisition module. It features a built-in web server, which allows easy configuration, I/O monitoring and I/O control on a regular web browser. The web HMI function provides an easy user interface where no programming skills are needed. Users can easily create dynamic and attractive web pages for I/O monitoring and I/O control. It offers easy access for users anytime and anywhere! In addition, ET-7017-10 supports Modbus TCP protocol which allows seamless integration with SCADA software.

![]()
| Software | |
|---|---|
| Built-in Web Server | Yes |
| CPU Module | |
|---|---|
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
|---|---|
| 2-way Isolation | Ethernet: 1500 VDC I/O: 2500 VDC |
| EMS Protection | |
|---|---|
| EFT (IEC 61000-4-4) | 4 kV for Power Line |
| ESD (IEC 61000-4-2) | 4 kV Contact for Each Terminal 8 kV Air for Random Point |
| Surge (IEC 61000-4-5) | 0.5 kV for Power Line |
| LED Indicators | |
|---|---|
| Status | Run, Ethernet |
| Analog Input | |
|---|---|
| Channels | 10 differential or 20 single-ended (Note1), software selectable |
| Type | Voltage Current |
| Range | 150 mV, 500 mV, 1 V, 5 V, 10 V 20 mA, 0 to 20 mA, 4 to 20 mA (Jumper Selectable) |
| Resolution | 16-bit |
| Accuracy | Normal Mode: 0.1% Fast Mode: 0.5% or better |
| Sampling Rate | Normal Mode: 10 Hz (total channels) Fast Mode: 50 Hz (total channels) |
| Input Impedance | Voltage: 2 M (Differential), 1 M (Single-ended) Current: 125 |
| Common Voltage Protection | 200 VDC |
| Overvoltage Protection | Differential: 240 Vrms Single-ended: 150 Vrms |
| Overcurrent Protection | 50 mA at 110 VDC (max.) |
| Individual Channel Configuration | Yes |
| Open Wire Detection | For 4 to 20 mA only |
| Isolation | 400 VDC, Virtual Channel to Channel Isolation |
| Ethernet | |
|---|---|
| Ports | 1 x RJ-45, 10/100 Base-TX |
| Access Control | ID, Password and IP Filter |
| Protocol | Modbus TCP, Modbus UDP |
| Power | |
|---|---|
| Reverse Polarity Protection | Yes |
| Consumption | 2.8 W (max.) |
| Powered from Terminal Block | +10 to +30 VDC |
| Mechanical | |
|---|---|
| Dimensions (mm) | 72 x 123 x 35 (W x L x H) |
| Installation | DIN-Rail mounting |
| Environment | |
|---|---|
| Operating Temperature | -25 +75 C |
| Storage Temperature | -30 +80 C |
| Humidity | 10 to 90% RH, Non-condensing |