| Share On: | |
|---|---|
| Categories: | Remote Ethernet Modbus TCP I/O Modules | Modbus TCP Based Dual Ethernet Port I/O Modules |
| Review: | Write your review |
| Resources: |
Providing various digital I/O functions, the ET-2251 module is an IP-based Ethernet I/O monitoring and control module. The module can be remotely controlled through a 10/100 M Ethernet network by using Modbus TCP/UDP protocol. Modbus has become a de facto standard communications protocol in industry, and is now the most commonly available means of connecting industrial electronic devices. This makes the ET-2251 module perfect integration with the HMI, SCADA, PLC and other software systems.
The ET-2251 provides 16 wet contact & dry contact Digital Input channels. With 2 Ethernet ports, the ET-2251 allows daisy chain connection which permits the flexibility in locating devices, eases installation and lowers infrastructure costs. It features 8 kV ESD protection, 4 kV EFT protection, 3 kV surge and 3000 VDC I/O isolation are also provided to enhance noise protection capabilities in industrial environments. Each input channel can be used as a 32-bit counter.
The module can be used to create DI to DO pair-connect through the Ethernet. After configuration, the ET-2251 module can poll the status of the local DI channels and then use the Modbus/TCP protocol to continuously write to the remote DO devices. It is equipped with removable terminal block connector for easy and robust wiring in industrial situations, and features a powerful 32-bit ARM MCU to handle efficient network trafficking.
| System | |
| CPU | 32-bit ARM |
| Communication | |
| Ethernet Port | 2 x RJ-45, 10/100 Base-TX, Swtich Ports |
| Protocol | Modbus TCP, Modbus UDP |
| Security | Password and IP Filter |
| I/O Pair Connection | Yes (Push, Polling) |
| Dual Watchdog | Yes, Module, Communication (Programmable) |
| LAN Bypass | Yes |
| LED Indicators | |
| for System Running | Yes |
| for Ethernet Link/Act | Yes |
| for DI/DO status | Yes |
| 2-Way Isolation | |
| Ethernet | 1500 VDC |
| I/O | 3000 VDC |
| EMS Protection | |
| ESD (IEC 61000-4-2) | ±8 kV Contact for Each Terminal and ±16 kV Air for Random Point |
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| Surge (IEC 61000-4-5) | ±3 kV for Power Line |
| Power Requirements | |
| Reverse Polarity Protection | Yes |
| Powered from Terminal Block | +10 ~ +30 VDC |
| Consumption | 2.9 W |
| Mechanical | |
| Dimensions (L x W x H) | 127 mm x 33 mm x 99 mm |
| Installation | DIN-Rail or Wall mounting |
| Environmental | |
| Operating Temperature | -25 ~ +75°C |
| Storage Temperature | -30 ~ +80°C |
| Humidity | 10 ~ 90% RH, Non-condensing |
| Digital Input/Counter | ||
| Channels | 16 | |
| Contact | Wet Contact/Dry Contact | |
| Sink/Source (NPN/PNP) | Sink/Source | |
| On Voltage Level | +5 VDC ~ +50 VDC | |
| Off Voltage Level | +1 VDC Max. | |
| Input Impedance | 7.5 kΩ | |
| Counters | Max. Count | 4,294,967,295 (32 bits) |
| Max. Input Frequency | 3 kHz | |
| Programmable Digital Filter | 1 ~ 6500 ms (0.08 Hz ~ 500 Hz) | |
| Overvoltage Protection | +70 VDC | |