| Share On: | |
|---|---|
| Categories: | Power Supplies |
| Review: | Write your review |
| Resources: |
| Model | DR-120-48 |
| Input | |
| Voltage range | 88 ~ 132 VAC/176 ~ 264 VAC by switch 248 ~ 370 VDC |
| Frequency range | 47 ~ 63Hz |
| Efficiency (Typ.) | 84 % |
| AC Current (Typ.) | 2.6 A/115 VAC 1.6 A/230 VAC |
| Inrush Current (Typ.) | Cold Start 20 A/115 VAC 40 A/230 VAC |
| Leakage current | <3.5 mA / 240 VAC |
| Output | |
| DC Voltage | 48 V |
| Rated Current | 2.5 A |
| Current Range | 0 ~ 2.5 A |
| Rated power | 120 W |
| Ripple & noise (max.) Note.2 | 100mVp-p |
| Voltage ADJ. range | 48 ~ 53 V |
| Voltage Tolerance Note.3 | ±1.0% |
| Line Regulation | ±0.5% |
| Load regulation | ±1.0% |
| Setup, rise Time Note.5 | 500 ms, 70 ms/230 VAC 500 ms, 70 ms/115 VAC at full load |
| Hold up time (Typ.) | 36 ms/230 VAC 32 ms/115 VAC at full load |
| Protection | |
| Overload | 105 ~ 150% rated output power |
| Protection type : Constant current limiting, recovers automatically after fault condition is removed | |
| Over voltage | 58 ~ 65 V |
| Protection type : Shut down o/p voltage, re-power on to recover | |
| Environmental | |
| Working temp. | -10 ~ +60 °C (Refer to output load derating curve) |
| Working humidity | 20 ~ 90% RH non-condensing |
| Storage TEMP., humidity | -20 ~ +85 °C , 10 ~ 95% RH |
| TEMP. Coefficient | ±0.03%/°C (0 ~ 50°C) |
| Vibration | 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
| Safety & EMC (Note 4) | |
| Safety standards | UL508, UL60950-1, TUV EN60950-1 Approved |
| Withstand voltage | I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
| Isolation resistance | I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500 VDC |
| EMI Conduction & Radiation | Compliance to EN55011,EN55022 (CISPR22) Class B |
| Hsrmonic current | Compliance to EN61000-3-2,-3 |
| EMS immunity | Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2) Heavy industry level, criteria A |
| DC OK Relay Contact | |
| Contact Close | When the output voltage reaches the adjusted output voltage. |
| Contact Open | When the output voltage drop below 90% output voltage. |
| Contact Ratings (max.) | 30V/1A resistive load |
| Others | |
| MTBF | 136.8Khrs min. MIL-HDBK-217F (25°C) |
| Dimensions (W x H x D) | 65.5 x 125.2 x 100 mm |
| Packing | 0.79 Kg; 20 pcs/16.5 Kg/1.1 CUFT |
| NOTE | |
|
|
| Terminal Pin. No Assignment (TB1) | Terminal Pin. No Assignment (TB2) | ||||||||||||||
|
|
Output Derating |
Static Characteristics (24V) |
![]() |
![]() |
Our mission is to provide the absolute best customer experience in industrial automation and electronics, without exception.
Subscribe to our mailing list today and join thousands of others who want to stay up-to-date with the latest news in data acquisition and industrial data communication.
Add a review