| Share On: | |
|---|---|
| Categories: | Motion, Temperature and Leak Detection Sensors | CL & DL Series Environmental Data Logger |
| Review: | Write your review |
| Resources: |
The DL-302 is a data logger module designed to accurately measure CO2 (carbon dioxide), temperature and humidity sensor/detector. It contains RS-485, Ethernet and PoE communication interfaces together with a 2.8" LCD Touch Screen display that can be used to display a variety of CO2, temperature and humidity measurements. The data storage memory can store up to 600,000 CO2, temperature and humidity records. The Data Logger Utility is included to allow retrieval and display of data in a powerful chart format that can be exported to Excel.
The DL-302 data logger can work with Android and iOS mobile devices which allow users to view real time CO2, temperature and humidity data on their mobile devices. The Android and iOS Apps are included with DL-302.




iAir is designed for DL-302 data logger, and is now available on the App Store and Google Play for iOS and Android devices. iAir can retrieve data from DL-302 at any time and any place, and display real time data and messages on screen remotely to send daily schedules or instructions to the on-site operators for remote monitoring and control.

CO Measurement |
||
Range |
- |
|
Resolution |
- |
|
Accuracy |
- |
|
Response Time |
- |
|
Warm-up Time |
- |
|
CO2 Measurement |
||
| Range | 0 to 9999 ppm (NDIR) | |
| Resolution | 1 ppm | |
| Accuracy | ±30 ppm ±3% of measured value | |
| Response Time | 20 seconds | |
Warm-up Time |
60 seconds |
|
Temperature Measurement |
||
Range |
-10 to +50°C |
|
Resolution |
0.1% RH |
|
Accuracy |
±5% RH |
|
Relative Humidity Measurement |
||
Range |
0 to 100% RH |
|
Resolution |
Open-Collector (NPN) (100mA, 30V) |
|
Accuracy |
+30 V max |
|
Dew Point |
||
Range |
Calculated using temperature and relative humidity |
|
Resolution |
0.1°C |
|
System |
||
| CO Alarm | - | |
| CO2 Alarm | Yes | |
| Real Time Clock | Yes | |
| Data Logger | Yes, up to 450,000 records | |
| Relay Output | Form A×1, SPST 30 VDC @ 16 A or 250 VAC @ 16 A |
|
| Interface | RS-485/Ethernet/PoE | |
Main Machine Interface |
||
LCD |
2.8 TFT (Resolution 240 x 320 x 16), Defective Pixels <= 3 |
|
Backlight Life |
20,000 hours |
|
| Brightness | 160 cd/m2 | |
Touch Panel |
Yes |
|
Electrical |
||
Powered from Terminal Block |
+12 to +48 VDC |
|
| Powered from PoE | IEEE 802.3af, Class 1 (48 V) | |
| Power Consumption | PoE | 2.65 W (Max.) |
| Non-PoE | 2.14 W (Max.) | |
Mechanical |
||
Dimensions (L x W x H) |
114 mm x 106 mm x 56 mm |
|
| Installation |
Desktop, DIN-Rail or Wall Mounting |
|
Environment |
||
| Operating Temperature | 0°C ~ +50°C (32°F ~ +122°F) | |
| Storage Temperature | -30°C ~ +75°C (-22°F ~ +167°F) | |
Humidity |
10 to 90% RH, Non-condensing |
|