FREE $30.00 Visa Gift Card with CODE: VISA for registered customer's FIRST-TIME purchase.

Cage/NCage Code 3FNF0

Orders ship within a week!

XP-8048-CE6

$3,199.00
Ethernet WinCE 6.0 R3 Core Based Win-GRAF PAC, VGA Port Modbus RTU/TCP protocol, redundant power inputs, has operatures of -25°C ~ +75°C (-13°F ~ +167°F)
Availability: IN STOCK | FASTEST DELIVERY : Sunday, Oct 11 | Enter ZIP below for shipping options
Get Shipping Options
QTY
-
+
  • LX800, 500 MHz CPU
  • Windows CE 6.0 R3 Core
  • Embedded Win-GRAF SoftLogic (IEC 61131-3)
  • Hard Real-Time Capability
  • VGA Port Output
  • Modbus RTU/TCP (Master, Slave)
  • Support Soft-GRAF HMI
  • Redundant Power Inputs
  • Support Dual PAC Redundant System
  • Operating Temperature: -25 ~ +75 °C

The Win-GRAF XPAC-8000-CE6 Series (XP-8048-CE6/XP-8348-CE6/XP-8748-CE6) is the new generation WinCE 6.0 based Win-GRAF XPAC-CE6 (Programmable Automation Controller) from ICP DAS. Each is equipped with an AMD LX800 500 MHz CPU running a Windows CE 6.0 R3 Core operating system, a variety of input/output ports (VGA, USB, Ethernet, RS-232/485), and a range of I/O slots (0/3/7) that can be used to integrate high performance parallel I/O modules (high profi le I-8K Series) or serial I/O modules (high profi le I-87K series).

The benefits of running Windows CE 5.0 on a XPAC device include hard real-time capability, achievable deterministic control and allowing PAC can have a PC-like window displays and operating environment. The PACs are capable of running Win-GRAF (IEC 61131-3 Standard) software to develop logic control applications, and also supporting M.S. VS 2008 or VS 2010 software (VB .NET, C#) to develop HMI and data management applications that can exchange data with Win-GRAF applications. So the application's design is more convenient and more practical.

Specifications

ModelsXP-8048-CE6XP-8348-CE6XP-8748-CE6
System Software
OSWindows CE 6.0 R3 Core
.Net Compact Framework3.5
Embedded ServiceFTP Server, ASP (Java Script, VB Script), SQL Compact Edition 3.5
SDK ProvidedDll for Visual Studio .Net 2005/2008
Multilanguage SupportEnglish, German, French, Spanish, Russian, Italian, Czech, Japanese, Korean, Simplified Chinese, Traditional Chinese
Development Software
Win-GRAF SoftwareWin-GRAFIEC 61131-3 standard
LanguagesLD, ST, FBD, SFC, IL
Support Soft-GRAF HMI : WP-8xx8, WP-5xx8, XP-8xx8-CE6, XP-9xx8-CE6 and VP-25W8/4138 PAC.
Max. Code Size2 MB
Scan Time15 ~ 50 ms (or more) for complex or large program
System MemoryOptions: VS.NET 2008/2010 (VB.NET, C.NET, C)
CPU Module
CPULX800, 500 MHz
System Memory512 MB DDR SDRAM
Dual Battery Backup SRAM512 KB; data valid up to 5 years (for retain variables)
Flash4 GB as IDE Master
EEPROM16 KB
CF CardYes, support up to 32 GB
RTC (Real Time Clock)Provide second, minute, hour, date, day of week, month, year
64-bit Hardware Serial NumberYes, for Software Copy Protection
Dual Watchdog TimersYes
Rotary SwitchYes (0 ~ 9)
DIP Switch-Yes (8 bits)
VGA & Communication Ports
VGAYes, (resolution: 1024 x 768, 800 x 600, 640 x480)
EthernetRJ-45 x 2, 10/100/1000 Base-TX (Auto-negotiating, Auto MDI/MDI-X, LED indicators)
USB 2.02
COM 1RS-232 (RxD, TxD and GND); 
non-isolated
Internal communication with the high profile I-87K series modules in slots
COM 2RS-232 (RxD, TxD and GND); non-isolated
COM 3RS-485 (Data+, Data-) with internal self-tuner ASIC; 3000 VDC isolated
COM 4RS-232/RS-485 (RxD, TxD, CTS, RTS and GND for RS-232, Data+ and Data- for RS-485); 
non-isolated
COM 5RS-232 (RxD, TxD, CTS, RTS, DSR, DTR, CD, RI and GND); non-isolated
I/O Expansion Slots
Slot Number037
Hot Swap 
Will be available soon
Note: For High Profile I-8K and I-87K Modules Only
Mechanical
Dimensions (W x L x H)137 mm x 132 mm x 125 mm231 mm x 132 mm x 125 mm355 mm x 132 mm x 125 mm
InstallationDIN-Rail or Wall Mounting
Environmental
Operating Temperature-25°C ~ +75°C (-13°F ~ +167°F)
Storage Temperature-30°C ~ +80 °C (-22°F ~ 176°F)
Ambient Relative Humidity10 ~ 90% RH, non-condensing
Power
Input Range10 ~ 30 VDC
Isolation1 kV
Redundant Power InputsYes, with one power relay (1 A @ 24 VDC) for alarm
Capacity15 W35 W35 W
Consumption14.4 W14.4 W16.8 W

Win-GRAF Specification

CPU Module
NET ID1 ~ 255, for Modbus TCP/RTU Slave, user-assigned.
Modbus TCP MasterA max. of 200 IP links to access/control the devices supporting Standard Modbus TCP Slave protocol.
Modbus RTU/ASCII MasterA max. of 32 ports: COM1 ~ 33 () to connect other Modbus Slave devices(Like M-7000).
Recommend connecting no more than 32 devices in each port for better scan rate
Modbus RTU/SlaveA max. of 16 ports: COM1 ~ 33 () for connecting SCADA/HMI/OPC Server.
Modbus TCP/SlaveTwo Ethernet ports (LAN1 & LAN2) support up to 64 connections. If the PAC uses 1 connection to connect each PC/HMI, it can connect up to 64 PCs/HMIs; If the PAC uses 2 connections to connect each PC/HMI, it can connect up to 32 PCs/HMIs; If one of the Ethernet port malfunctions, the other one can still be used to connect the PC/HMI.
User-define ProtocolCustom protocols can be applied at COM1~ 33 () by using Serial communication functions or function blocks.
DCON Remote I/OA max. of 16 RS-485 ports: COM1 ~ 33 (). Each port can connect max. 50 nos I-7000 series modules or 
50 nos I-87xxxW I/O modules in expansion units (I-87K4, I-87K8, I-87K9, RU-87P8, RU-87P4).
Recommend connecting no more than 32 modules in each port for better scan rate.
Local I/O ModulesSupports only high profile I/O modules. Slot 1 ~ 7 supports I-8xxxW parallel I/O modules and I-87xxxW serial I/O modules. (Refer Optional I/O List)
App ProtectionUsing the unique 64-bit (8 bytes) PAC serial number to generate a protection password by your own algorithm to protect your Win-GRAF application. Then, if someone intend to copy your application in the PAC to another new PAC with the same PAC model, this application will not work properly in that new PAC.
Redundancy2 XP-8xx8-CE6 can set a redundant system, when one is damaged or crashes, the other can still take up and continue the work. The system offers 3-line communication redundancy, LAN1, LAN2 and Alive Port (COM5), as long as one of the three communication lines still connects normally, this redundant system can normally control the process. The redundant system provides a public IP address that allows SCADA/ HMI software to access it without needing to determine which one is the Active IP.
Data BindingExchange data between ICP DAS Win-GRAF PAC via Ethernet ports (LAN1 and LAN2). The data transmission is event triggered. It is much efficient than polling way. Beside, user can setup the Redundant Binding in two ethernet ports by Software, then if one Ethernet port fail, it can switch to use the other port.
On Line ChangeFor application field that not allowed to stop the Win-GRAF program and wish to run a new program modified a little from the original program.
Modbus RTU I/OWhen software enables Modbus RTU Master function, the PAC can connect ICP DAS M-7000 and tM series and LC series I/O modules which support Modbus RTU protocol
Modbus TCP I/OWhen software enable Modbus TCP Master function, the PAC can connect ICP DAS I-8KE4/8-MTCP, PETL-7000, tPET/tET series I/O modules which support Modbus TCP protocol.
Schedule ControlSupports the "Schedule-Control Utility" (free) to implement schedule control. Each PAC can control max. 10 Targets (devices) with different schedule settings in each day / holiday / special day / season / year.
Retain VariableBuilt-in the fast retain memory that can retain up to 12,000 Win-GRAF variables.
File Access and Data LogThe Win-GRAF supports file operation functions to read/write files in the PACs micro_SD or flash memory to do data log or file access.
Soft-GRAF HMISupport to run HMI program (developed by the Soft-GRAF Studio) together with the Win-GRAF logic-control program in the same PA
Optional I/O List
Digital Input (DI)I-8040W, I-8046W, I-8051W, I-8052W, I-8053W, I-8053PW, I-87040W, I-87040PW, I-87046W,
I-87051W, I-87052W, I-87053W, I-87053PW, I-87053W-A2, I-87053W-A5, I-87053W-E5
Digital Input/Out (DIO)I-8042W, I-8050W, I-8054W, I-8055W, I-87042W, I-87054W, I-87055W
Digital Output (DO)I-8037W, I-8041W, I-8041AW, I-8056W, I-8057W, I-87037W, I-87041W, I-87057W, I-87057PW
Relay OutpuI-8060W, I-8063W, I-8064W, I-8068W, I-8069W, I-87061W, I-87061PW, I-87063W, I-87064W,
I-87065W, I-87066W, I-87068W, I-87068W-2A, I-87069W, I-87069PW
AC InputI-8058W, I-87053W-AC1, I-87058W, I-87059W
Analog Input (AI)I-8017DW, I-8017HW, I-8017HCW, I-87017W, I-87017RW, I-87017RCW, I-87017DW, I-87017EW,
I-87018W, I-87018RW, I-87018PW, I-87018ZW, I-87019PW, I-87019RW, I-87019ZW
Analog Output (AO)I-8024W, I-87024CW, I-87024UW, I-87024DW, I-87024RW, I-87024W, I-87028CW, I-87028UW,
I-87028VW, I-87028VW-20V
Multifunction (DIO, AIO)I-87026W
Temperature InputThermisterI-87005W
RTDI-87013W, I-87015W, I-87015PW
T/CI-87018W, I-87018RW, I-87018PW, I-87018ZW, I-87019PW, I-87019RW, I-87019ZW
Strain GaugeI-87016W
Counter/Frequency InputI-8084W, I-87082W, I-87084W
Encoder InputI-8093W
PWM OutputI-8088W
Communiation ModuleI-8112iW, I-8114W, I-8114iW, I-8142iW, I-8144iW
Temperature & Humidity InputDL-100T485, DL-100T485-W, DL-100T485P, DL-100T485P-W (DCON Protocol)
DL-100TM485, DL-100TM485-W, DL-100TM485P, DL-100TM485P-W (Modbus RTU Protocol)
Note:COM6 ~ COM33 ports are located in the expansion boards (I-8142iW, I-8144iW, I-8112iW, I-8114W, I-8114iW)
             if they are installed in slot 1 ~ 7 of XP-8xx8-CE6.
 Only XP-8048-CE6 has COM1.
 ICP DAS recommends using NS-205/NS-208 or RS-405/408 (Ring Switch) Industrial Ethernet Switches.

Add a review

Your email address will not be published. Required fields are marked *

Overall ratings
Select Rating *
You must be signed in to review! Click here to sign in.
Related Products
XP-8748-CE6
$3,499.00
XP-8348-CE6
$3,399.00
Win-GRAF
$2,399.00
Connect with us

Our mission is to provide the absolute best customer experience in industrial automation and electronics, without exception.

Join Our Newsletter

Subscribe to our mailing list today and join thousands of others who want to stay up-to-date with the latest news in data acquisition and industrial data communication.

About Us

ICP DAS USA is a leading manufacturer of industrial data acquisition, data communication, programmable controllers, wireless and software solutions.