| Share On: | |
|---|---|
| Categories: | Smart Power Meters |
| Review: | Write your review |
| Resources: |
The PM-3133-100-MTCP has officially been phased out and no longer available. The suggested replacement is PM-3133-100P-MTCP
PM-3133-100-MTCP is a three-phase smart power meter communicable over Modbus TCP for power monitoring. With its high accuracy (<0.5%, PF=1), the PM-3133 series products can be applied both on low voltage primary side and/or medium/high voltage secondary side and enable the users to obtain in real time the reliable and accurate energy consumption readings from the monitored equipments. These compact size and cost effective Power Meters are equipped with wired clip-on CT (supports input current up to 200A) and standard Modbus TCP communication protocol for easy integration. It works with input voltages ranging from 10V ~ 500V, supporting a wide range of applications.
| Model | PM-3133-100-MTCP | |
| AC Power Measurement | ||
| Wiring | 1P2W-1CT, 1P3W-2CT, 3P3W-2CT, 3P3W-3CT and 3P4W-3CT | |
| Measurement Voltage | 10 ~ 500 V (CAT III) | |
| Measurement Current | CT 10 mm (60 A); CT16 mm (100 A); CT24 mm (200 A) | |
| Measurement Frequency | 50-60 Hz | |
| W Accuracy | Greater than 0.5% (PF=1) | |
| Starting Current | >0.03A (60A ) | |
| Power Parameter Measurement | True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF) | |
| Data Update Rate | 1 Second | |
| Communication | ||
| Dimension | Protocol | - |
| Baud rate | - | |
| Data forat | - | |
| Isolation | - | |
| Bias Resistor | - | |
| Ethernet | Protocol | Modbus TCP |
| PoE | Modbus TCP | |
| Alarm Output | ||
| Power Relay | Form A (Normal Open) x 2; Relay Contact Voltage Range: 5 A @ 250 VAC (47 ~ 63Hz), 5 A @ 30 VDC | |
| Aux Power | ||
| Input Range | +12 ~ 48 VDC or PoE | |
| Power Consumption | 4 W | |
| Dimensions (W x L x H) | 127 mm x 105 mm x 33 mm | |
| Environment | ||
| Operating Temperature | -10 ~ +70 °C (14 °F ~ 158 °F) | |
| Storage Temperature | -25 ~ +80 °C (-13° F ~ 176° F ) | |
Our mission is to provide the absolute best customer experience in industrial automation and electronics, without exception.
Subscribe to our mailing list today and join thousands of others who want to stay up-to-date with the latest news in data acquisition and industrial data communication.
Add a review
Your email address will not be published. Required fields are marked *