| Share On: | |
|---|---|
| Categories: | I-7000 Remote Data Acquisition Modules via RS-485 / DCON Protocol |
| Review: | Write your review |
| Resources: |
I-7065BD is intelligently designed to provide signal conditioning system monitoring and safe value settings. I-7065BD is a cost-effective solution for a wide range of valuable industrial control signals and systems. The DCON utility can help users to configure and test I-7065BD DC-SSR relay output module. Plenty of library functions and demo programs are provided to let users develop programs easily under Windows, Linux and DOS operating systems. The communication interface is modbus protocol via RS-485. Users may mount the modules on a DIN rail, panel or wall. Modules have a screw-terminal block to connect to the signals.
| CPU Module | |
|---|---|
| Watchdog Timer | Module, Communication (Programmable) |
| Display | |
|---|---|
| Type | I/O LED Indicator |
| Isolation | |
|---|---|
| Intra-module Isolation | 3750 VDC |
| EMS Protection | |
|---|---|
| EFT (IEC 61000-4-4) | 2 kV for Power Line |
| ESD (IEC 61000-4-2) | 4 kV Contact for Each Terminal 8 kV Air for Random Point |
| LED Indicators | |
|---|---|
| Status | 1 x Power and Communication 9 x Digital Input/Relay Output |
| Digital Input/Counter | |
|---|---|
| Channels | 4 |
| Type | Wet Contact |
| Sink/Source (NPN/PNP) | Sink/Source |
| ON Voltage Level | +1 VDC Max. |
| OFF Voltage Level | +4 +30 VDC |
| Max. Counts | 65535 (16-bit) |
| Frequency | 100 Hz |
| Min. Pulse Width | 5 ms |
| Input Impedance | 3 k |
| Overvoltage Protection | 35 VDC |
| Relay Output | |
|---|---|
| Channels | 5 (Form A) |
| Type | DC-SSR |
| Contact Rating | 3 30 VDC @ 1A |
| Leakage Current | 0.1 mA |
| Operate Time | 1 ms |
| Release Time | 1 ms |
| Electrical Endurance | Long Life, No Arcing, No Bounce, No Switching Noise |
| Power on Value | Programmable |
| Safe Value | Programmable |
| COM Ports | |
|---|---|
| Ports | 1 x RS-485 |
| Baud Rate | 1200 115200 bps |
| Data Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1) |
| Protocol | DCON |
| Power | |
|---|---|
| Reverse Polarity Protection | Yes |
| Input Range | +10 +30 VDC |
| Consumption | 1.0 W |
| Mechanical | |
|---|---|
| Dimensions (mm) | 72 x 123 x 35 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
|---|---|
| Operating Temperature | -25 +75 C |
| Storage Temperature | -40 +85 C |
| Humidity | 10 95% RH, Non-condensing |