| Share On: | |
|---|---|
| Categories: | I-7000 Remote Data Acquisition Modules via RS-485 / DCON Protocol |
| Review: | Write your review |
| Resources: |
I-7019R provides cost-effective protection and conditioning for a wide range of valuable industrial control signals and systems. I-7019R provides 4KV of ESD protection. The individual channels are configurable; the user selects the type and range remotely by issuing commands from the host. Fewer modules may be used for different applications. The user may mount the modules on a DIN rail, panel or wall. Modules have a screw-terminal block to connect to the signals. I-7019R comes with FREE EZ Data Logger Software.
| Analog Input | |
| Input Channels | 8 differential |
| Input Type | Voltage Input Range:
+/-15mV, +/-50mV, +/-100mV, +/-150mV, +/-500mV +/-1V, +/-2.5V, +/-5V, +/-10V Current Input Range: ± 20mA, 0~20mA, 4~20mA (Jumper Selectable) Thermocouple Types: J, K, T, E, R, S, B, N, C, L, M,LDIN43710 |
| Resolution | 16-bit |
| Sampling Rate | 8 samples/ second (Total) |
| Accuracy | +/-0.1% |
| -3dB Band Width | 5.24Hz |
| Zero Drift | 0.5uV/°C |
| Span Drift | 25ppm/°C |
| Common Mode Rejection | 86dB |
| Normal Mode Rejection | 100dB |
| Input Impedance | Voltage Input: >2M ohm, Current Input: 125 Ohm |
| Over Voltage Protection | 240 Vrms |
| Open Thermocouple Detection | Yes |
| Individual Channel Configuration | Yes |
| 4KV ESD Protection | Yes, Contact for each terminal. |
| Intra-module Isolation, Field to Logic | 3000 VDC |
| Interface | |
| Interface | RS-485 |
| Format | N, 8, 1 |
| Baud Rate | 1200 ~ 115200bps |
| LED Display | |
| 1 LED as Power/ Communication indicator | |
| Power | |
| Input | +10 to +30 Vdc |
| Power Consumption | 1.2W |
| Environment | |
| Operating temperature | -25 to 75°C |
| Storage temperature | -40 to 85°C |
| Humidity | 5 to 95% RH, non-condensing |
| Type Code | Thermocouple Type | Temperature Range °C |
| 0E | Type J | -210 ~ +760 |
| 0F | Type K | -270 ~ +1372 |
| 10 | Type T | -270 ~ +400 |
| 11 | Type E | -270 ~ +1000 |
| 12 | Type R | 0 ~ +1768 |
| 13 | Type S | 0 ~ +1768 |
| 14 | Type B | 0 ~ +1820 |
| 15 | Type N | -270 ~ +1300 |
| 16 | Type C | 0 ~ +2320 |
| 17 | TypeL | -200 ~ +800 |
| 18 | TypeM | -200 ~ +100 |
| 19 | Type L2 (DIN 43710) | -200 ~ +900 |
Our mission is to provide the absolute best customer experience in industrial automation and electronics, without exception.
Subscribe to our mailing list today and join thousands of others who want to stay up-to-date with the latest news in data acquisition and industrial data communication.
Add a review
Your email address will not be published. Required fields are marked *