| Share On: | |
|---|---|
| Categories: | I-7000 Remote Data Acquisition Modules via RS-485 / DCON Protocol |
| Review: | Write your review |
| Resources: |
I-7018R is an analog input module with an extremely excellent protection mechanism where over voltage protection is up to 240 Vrms. Its input type includes current, voltage as well as thermocouple. Naturally, I-7018R is an upgraded version of I-7018; the only difference is that the I-7018R is much more suitable for critically harsh environment! Moreover, a newly-added feature for open thermocouple detection makes I-7018R more sweet than ever. I-7018R also has qualifi cation for 4KV ESD protection and 3000 VDC intramodule isolation.
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote diagnosis, Testing Equipment.
I-7018R comes with FREE EZ Data Logger Software.
| CPU Module | |
|---|---|
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
|---|---|
| Intra-module Isolation | 3000 VDC |
| EMS Protection | |
|---|---|
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal |
| Surge (IEC 61000-4-5) | ±0.5 kV for Power Line |
| LED Indicators | |
|---|---|
| Status | 1 x Power and Communication |
| Analog Input | |
|---|---|
| Channels | 8 Differential |
| Type | Voltage Current Thermocouple |
| Sensor Type | Thermocouple: J, K, T, E, R, S, B, N, C |
| Range | Voltage: ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V Current: ±20 mA, 0 ~ +20 mA, +4 ~ +20 mA (requires an optional external 125 resistor) |
| Resolution | 16-bit |
| Accuracy | ±0.1% of FSR |
| Sampling Rate | 10 Hz (Total) |
| Input Impedance | > 400 k |
| Common Voltage Protection | 200 VDC |
| Overvoltage Protection | 240 Vrms |
| Overcurrent Protection | Yes |
| Individual Channel Configuration | Yes (Note1) |
| Open Wire Detection | For Thermocouple Only (Software Selectable, Note2) |
| COM Ports | |
|---|---|
| Ports | 1 x RS-485 |
| Baud Rate | 1200 ~ 115200 bps |
| Data Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1) |
| Protocol | DCON |
| Power | |
|---|---|
| Reverse Polarity Protection | Yes |
| Input Range | +10 ~ +30 VDC |
| Consumption | 1.0 W |
| Mechanical | |
|---|---|
| Dimensions (mm) | 72 x 123 x 35 (W x L x H) |
| Installation | DIN-Rail Mounting |
| Environment | |
|---|---|
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -40 ~ +85 °C |
| Humidity | 10 ~ 95% RH, Non-condensing |
Note:
For highly-accurate thermocouple measurement, ICP DAS recommends selecting the I-7018Z/I-7019Z module, which features automatic cold-junction compensation for each channel, ensuring consistent and stable temperature output..
Note1: Firmware version B4.2 or later.
Note2: Firmware version B4.5 or later.