| Share On: | |
|---|---|
| Categories: | I-9000 Remote I/O modules |
| Review: | Write your review |
| Resources: |
The I-9053P is equipped with 16 -channels digital input, designed for both dry and wet contact, with an effective distance for dry contact of up to 500 meters. All channels feature photocouple isolation.
The I-9053P provides 16 LED indicators that can be used to monitor the DI channel status. 4 kV ESD protection and 3750 Vrms intramodule isolation are also provided to enhance noise immunity capabilities in industrial environments.
LED Indicators
System LED Indict
1 LED as Power Indicator
I/O LED Indicator
16 LEDs as Digital Input Indicators
Isolation
Intra-module Isolation, Field-to-Logic
3750 Vrms
EMS Protection
ESD (IEC 61000-4-2)
±4 kV Contact for each Terminal
±8 kV Air for Random Point
Power
Power Consumption
1 W Max.
Mechanical
Dimensions (L x W x H)
144 mm x 31 mm x 134 mm
Environment
Operating Temperature
-25°C ~ +75°C
Storage Temperature
-40°C ~ +85°C
Humidity
10 ~ 90% RH, non-condensing
Digital Input
Channels
16
Sink/Source (NPN/PNP)
Sink
Sink/Source(NPN/PNP)
Sink/Source
Input Type
Dry, Wet
Dry Contact
On Voltage Level
Close to GND
Off Voltage Level
Open
Wet Contact
On Voltage Level
+19 VDC ~ +30 VDC
Off Voltage Level
+11 VDC Max.
Input Impedance
3 KΩ, 1W
Effective Distance for Dry Contact
500 m Max.
Low Pass Filter
Response time
OFF to ON
1 ms/5 ms/10 ms/20 ms/40 ms/70 ms (by Jumper select) or CPU parameter setting
Default Setting is 10ms
ON to OFF
1 ms/5 ms/10 ms/20 ms/40 ms/70 ms (by Jumper select) or CPU parameter setting
Default Setting is 10ms