How do I configure two tGW-715i gateways for a pair-connection or serial bridge application?

A pair-connection can carry serial Modbus communications over an Ethernet or routed TCP/IP connection. This is useful when two serial devices must exchange Modbus messages but are too far apart for a direct serial cable.

You generally need two compatible gateways, one at each location.

Gateway A — Client Mode

  1. Assign the gateway a unique network IP address.
  2. Configure its serial port for the local device’s required serial interface, baud rate, data format, and Modbus protocol.
  3. Open Port1.
  4. Set Application Mode to Client.
  5. Select the appropriate network protocol.
  6. Enter Gateway B’s IP address under Remote Server IP.
  7. Set Remote TCP Port to the listening TCP port configured on Gateway B, normally 502 if using the default.
  8. Click Submit.

The Client gateway initiates the TCP connection.

Gateway B — Server Mode

  1. Assign a different, unique IP address.
  2. Configure its serial port for the attached device.
  3. Set Application Mode to Server.
  4. Confirm that its listening TCP port and network settings are correct.
  5. Click Submit.

The serial settings at each end should match the device attached to that particular gateway; they do not necessarily have to be identical at both locations.

The manual includes examples of pair-connections using different baud rates and serial interfaces.

Troubleshooting Tip: Verify IP connectivity between the gateways, TCP port access through any firewalls, correct Client/Server roles, and serial wiring at both ends. A functioning Ethernet link alone does not guarantee that the remote serial devices are communicating correctly.