The configuration is similar to the RTU application, but the gateway’s serial protocol must be set to Modbus ASCII.
1. Discover the tGW-715i with eSearch and open its web interface.
2. Configure the module’s network settings.
3. Select Port1.
4. Set the baud rate, data size, parity, and stop bits to match the serial device.
5. Change the serial Protocol selection to Modbus ASCII.
6. Leave Application Mode set to Server for the normal Ethernet-master-to-serial-slave configuration.
7. Click Submit.
8. Configure your Modbus TCP master to connect to the gateway’s IP address and TCP port, normally 502 .
The Ethernet master continues to send Modbus TCP requests; the gateway converts them to Modbus ASCII on the serial side and converts the responses back for the Ethernet master.
Troubleshooting tip: Do not select Modbus RTU on the serial side if the connected device expects ASCII framing. Also verify the device’s serial parameters and ensure it supports the function codes and register addresses requested by the master.