The manufacturer’s user manual documents a reset procedure using the module’s physical Init/Run switch. This is a recovery procedure, not a routine troubleshooting step.
Before Resetting: Be aware that restoring factory defaults resets all configuration settings, including network and serial communication parameters. Save the current configuration beforehand if possible, and arrange an appropriate maintenance window.
Recovery Procedure
- Locate the Init/Run switch on the module.
- Move the switch to the Init position.
- Reboot the module to load factory-default settings.
- Use eSearch to find the gateway on the local network.
- Confirm that the module has returned to its default network configuration. The manual lists 192.168.255.1 as the default IPv4 address.
- Configure the IP address, subnet mask, and gateway as needed for the installation.
- Return the Init/Run switch to the Run position and reboot the module.
- Open the web interface and log in using the factory-default password, following the manual’s recovery instructions.
- Change the password and reconfigure the serial port, protocol, and application settings.
- Test both Ethernet and serial Modbus communication before returning the module to service.
Troubleshooting Tip: If the gateway still cannot be accessed after the reset, check its power, the PC’s IP configuration, and whether the PC is connected to the correct local network. Follow the exact recovery sequence in the current manual for your hardware and firmware version.