Yes. The tGW-715i supports up to 32 TCP connections (masters) per serial port, according to the manufacturer’s tGW-715i specification.
This allows multiple systems, such as an HMI, SCADA workstation, and data logging application, to access serial Modbus equipment through one gateway.
However, multiple TCP connections do not create additional physical serial bandwidth. Requests that need to use the same serial port still have to be managed across the shared serial interface.
Troubleshooting Tip: If each master works independently but response times deteriorate when all are active, test the system with fewer concurrent requests. Check serial bus utilization, queue timeouts, polling rates, and cache settings before assuming the gateway has failed.