Can multiple Modbus TCP masters communicate with the same tGW-715i simultaneously?

Yes. The tGW-715i supports up to 32 TCP connections (masters) per serial port, according to the manufacturer’s tGW-715i specification.

This allows multiple systems, such as an HMI, SCADA workstation, and data logging application, to access serial Modbus equipment through one gateway.

However, multiple TCP connections do not create additional physical serial bandwidth. Requests that need to use the same serial port still have to be managed across the shared serial interface.

Recommended Configuration Practices

  1. Assign the gateway a stable, unique IP address.
  2. Configure each master to use the correct TCP port and target slave address.
  3. Avoid excessive polling rates that place unnecessary load on the serial devices.
  4. Consider enabling Read Cache when several masters repeatedly request the same data and the cache’s freshness limitations are acceptable.
  5. Review response timeouts and queue behavior if requests are delayed during periods of heavy traffic.

Troubleshooting Tip: If each master works independently but response times deteriorate when all are active, test the system with fewer concurrent requests. Check serial bus utilization, queue timeouts, polling rates, and cache settings before assuming the gateway has failed.