What is the Read Cache function, and how do I configure it?

The Read Cache function stores previously retrieved data so the gateway can respond to repeated requests more quickly without unnecessarily querying the serial device every time.

It can be useful when multiple Ethernet-based masters frequently request the same data from the same serial slave. Caching reduces serial bus traffic and may improve response times.

How to Configure Read Cache

  1. Open the module’s web interface.
  2. Select Port1.
  3. Locate Read Cache (ms) in the Modbus TCP settings.
  4. Use an appropriate cache interval for the application.
  5. Set it to 0 to disable the cache if fresh readings are more important than the performance benefit.
  6. Click Submit and verify the behavior.

The manual lists a default cache interval of 980 ms. With caching enabled, repeated requests may return stored values instead of triggering an immediate new serial transaction.

When Should I Disable It?

Consider disabling or reducing caching when monitoring rapidly changing values, verifying real-time measurements, or troubleshooting inconsistent readings. Test the effect on both data freshness and serial network loading before selecting the final value.