The gateway provides several timing parameters on its Port1 configuration page. These control how long the module waits for a response, identifies serial message boundaries, and manages requests waiting to use the serial port.
300 ms
Maximum wait for the serial slave’s response before a timeout is reported.
4 bytes
Helps determine when a serial response has finished arriving.
0 ms
Adds idle time before the next serial request is sent.
1,000 ms
Limits how long a request can wait in the Modbus TCP request queue.
Character Timeout should be adjusted only when response framing or timing measurements indicate a need.
Queue Timeout is relevant when multiple masters or requests compete for access to the serial bus.
Troubleshooting Tip: Increasing every timeout is not necessarily the best solution. First determine whether the issue is a genuinely slow device, incorrect serial framing, a wiring problem, or excessive traffic.