What is the difference between Server mode and Client mode on the tGW-715i?

The Application Mode setting in the Pair-Connection Settings section determines how the serial port communicates with a remote network Modbus device.

Application mode
Function
Typical example
Server

Supports the normal Modbus TCP/UDP master-to-serial RTU/ASCII slave arrangement. It also acts as the server endpoint when used in a pair-connection.

SCADA software polls a serial Modbus meter over Ethernet.

Client

Initiates communication with a remote Modbus TCP/UDP slave for the reverse-direction application, or connects to a remote gateway configured as a pair-connection server.

A serial RTU master sends requests to a remote TCP slave.

To use Client mode, you normally need to select the network protocol and specify the remote server IP address and TCP port.

In Server mode, those remote-client fields are not used in the same way.

Important Distinction

These settings do not change the serial device into a different physical interface. You must still configure the appropriate serial communication parameters and wire the device correctly.

Troubleshooting Tip: If you are using a normal Ethernet-based Modbus master to poll a serial slave, start with the standard gateway configuration in Question 3. Do not switch to Client mode unless your application requires the serial master-to-network slave or pair-connection arrangement.