How do I configure the tGW-715i when a Modbus RTU master needs to communicate with a Modbus TCP slave?

This is a reverse-direction application compared with the conventional Modbus TCP-master-to-serial-slave arrangement. ICP DAS documents this configuration in its official tGW-700 Series FAQ.

For example, a serial Modbus RTU master may need to access a remote Modbus TCP slave through Ethernet.

Configuration procedure:

  1. Connect the serial Modbus RTU master to the tGW-715i’s serial port.
  2. Configure Port1 with the serial master’s baud rate, data size, parity, and stop bits.
  3. Set the serial protocol to Modbus RTU or Modbus ASCII, as applicable.
  4. In the Pair-Connection Settings section, change Application Mode to Client.
  5. Select TCP / IPv4 under Network Protocol if the destination is a Modbus TCP device on an IPv4 network.
  6. Enter the remote Modbus TCP slave’s IP address under Remote Server IP.
  7. Enter its TCP port under Remote TCP Port, normally 502.
  8. Click Submit.
  9. Test using the serial master and confirm that the remote TCP slave returns a valid response.

 

The gateway converts the serial masters requests for delivery over ethernet and converts the responses for the serial side.

 

Troubleshooting tip: Verify that the remote TCP device is reachable, that its TCP port is correct, and that it actually supports the requested Modbus operations. Also confirm that the serial master is communicating with tGW-715i using the correct serial protocol and framing.