How do I connect the tGW-715i to an RS-422 device?

RS-422 generally uses separate transmit and receive differential pairs, unlike a typical two-wire half-duplex RS-485 connection.

Use the applicable tGW-715i wiring diagram to connect the pairs:

  • Gateway TxD+ to the remote device’s RxD+.
  • Gateway TxD- to the remote device’s RxD-.
  • Gateway RxD+ to the remote device’s TxD+.
  • Gateway RxD- to the remote device’s TxD-.
  • Connect the signal reference as recommended by the equipment manufacturers.

Use twisted-pair wiring for the differential signals. Termination may be necessary at the receiving ends, depending on the cable, network layout, and equipment specifications.

 

Troubleshooting tip: If communication fails in one direction, check the corresponding transmit and receive pair separately. Reversed transmit/receive connections or incorrect differential polarity are common causes of problems. Also confirm that the equipment is actually configured for RS-422 rather than RS-485.