The tGW-715i supports an isolated RS-485 interface with automatic transmit-direction control. For a typical two-wire RS-485 network, use a twisted-pair cable and connect the differential data lines with the correct polarity.
Basic wiring procedure:
Some manufacturers label RS-485 connections A/B, while others use D+/D−. The meaning of A and B is not completely consistent across vendors, so verify the device documentation rather than relying on terminal letters alone.
Troubleshooting tip: If the gateway receives no replies, check data-line polarity first. Then examine the common reference, termination, cable topology, grounding, and possible electrical noise. Avoid unnecessary termination resistors and long branch connections.