The serial settings on Port1 must match the serial device or devices connected to the gateway. A mismatch can prevent communication even when the Ethernet connection and IP settings are correct.
In the web interface, select Port1 and configure:
Baud rate
An Ethernet-based PLC or SCADA master communicates with serial Modbus RTU slaves.
Data size
Must match the device’s serial data-bit setting.
Parity
Must match the configured parity, such as None, Even, or Odd.
Stop bits
Must match the device’s stop-bit setting.
Protocol
Select Modbus RTU or Modbus ASCII as required.
For example, if a meter uses 19,200 baud, 8 data bits, even parity, and 1 stop bit, configure the gateway to the same format.
Click Submit after making changes. Test with a single known-good Modbus request before returning the full application to service.
Troubleshooting tip: Check the actual device configuration or manual instead of assuming every serial Modbus device uses 9600 baud and 8N1.