How do I configure the tGW-715i to convert Modbus TCP requests to Modbus RTU?

This is the standard application when an Ethernet-based PLC, HMI, or SCADA master needs to communicate with one or more serial Modbus RTU slave devices.

Configuration procedure:

1. Connect the tGW-715i to the Ethernet network and power it using an approved power source.
2. Use the ICP DAS eSearch utility to discover the module and open its web configuration interface.
3. Configure its IP address, subnet mask, and gateway as required by your network.
4. Open the Port1 settings page.
5. Set the serial baud rate, data size, parity, and stop bits to match the connected RTU slave
devices. For example, 9600 baud, 8 data bits, no parity, 1 stop bit is a valid 8N1 configuration when supported by the devices.
6. Set the serial Protocol to Modbus RTU.
7. Keep Application Mode set to Server for the standard Ethernet-master-to-serial-slave application.
8. Click Submit to save the configuration.
9. Configure the Ethernet-based master to connect to the gateway’s IP address and TCP port, normally 502 .
10. Address the intended serial slave using its Modbus device address and issue a valid read or write request.

 

Troubleshooting tip: If the TCP connection works but Modbus requests time out, verify the serial device address, serial wiring, baud rate, parity, stop bits, and register/function-code settings first.