Which communication protocols and operating modes does the tGW-715i support?

The tGW-715i supports Modbus TCP/UDP master and slave roles and Modbus RTU/ASCII master and slave roles. Its supported application depends on how the serial port and pair-connection settings are configured.

The principal applications are:

Application
Typical use

Modbus TCP to Modbus RTU

An Ethernet-based PLC or SCADA master communicates with serial Modbus RTU slaves.

Modbus TCP to Modbus ASCII

An Ethernet-based master communicates with serial devices using Modbus ASCII.

Serial Modbus master to Modbus TCP slave

A serial RTU/ASCII master communicates with a Modbus TCP/UDP slave over Ethernet.

Pair-connection or serial bridge/tunnel

Two gateways carry serial Modbus communications between remote locations over TCP/IP.

For the standard Modbus TCP-to-serial application, the gateway’s pair-connection Application Mode normally remains set to Server. In the pair-connection settings, Server means the serial Modbus slave side is accessed by a network master; Client means the serial Modbus master side initiates communication with a remote network slave. These labels describe the pair-connection roles, not whether the device’s web configuration server is running.