The tGW-715i supports Modbus TCP/UDP master and slave roles and Modbus RTU/ASCII master and slave roles. Its supported application depends on how the serial port and pair-connection settings are configured.
The principal applications are:
Modbus TCP to Modbus RTU
An Ethernet-based PLC or SCADA master communicates with serial Modbus RTU slaves.
Modbus TCP to Modbus ASCII
An Ethernet-based master communicates with serial devices using Modbus ASCII.
Serial Modbus master to Modbus TCP slave
A serial RTU/ASCII master communicates with a Modbus TCP/UDP slave over Ethernet.
Pair-connection or serial bridge/tunnel
Two gateways carry serial Modbus communications between remote locations over TCP/IP.
For the standard Modbus TCP-to-serial application, the gateway’s pair-connection Application Mode normally remains set to Server. In the pair-connection settings, Server means the serial Modbus slave side is accessed by a network master; Client means the serial Modbus master side initiates communication with a remote network slave. These labels describe the pair-connection roles, not whether the device’s web configuration server is running.